Power Range
High specification bushings for use on Power Transformers. Robustly built, with enhanced over- voltage capability. Designation – oil / air outdoors Compliance Standards BS EN ISO 60137 Available Designs FF – Free-flow: utilises transformer’s own dielectric fluid. SC – Self contained: having its own oil conservator. The normal bushing attitude is vertically mounted. Most bushings in range can be used in horizontal position – see individual data sheets. For some voltages we are able to provide high current (HC) and very high current (VHC) versions. Insulators Insulator is one-piece ceramic porcelain with anti-fog / high creepage design. Standard porcelain colour is Brown. Grey porcelain is also available – consult us for lead times Metalwork Conductors are electro-tin plated. Fixings and fasters are anti-corrosion plated. Termination Most bushings are supplied with plain terminals enabling connection via flag, palm or block connectors. Lower current versions can be supplied with screwed terminals – if required. Fixation Bushings are supplied fitted with an aluminium flange with fixing holes drilled to accept transformer cover studs. Range Summary
|